Troubleshooting 175
57685
(0xe15
5)
DC input current
measurement
DC input current measurement is
out of range.
Connection is lost or sensor is
broken.
One or more DC input current
measurement has/have failed.
Aux. code (format XYZ) indicates
the failed power module.
If X = 1, measurement failed
due to calibration function
If X = 0, measurement is out of
range.
Y = indicates the module
number. E.g. 1 refers to
module 1.
Z = indicates DC input number.
For example, aux. code 112,
means calibration function
reported faulty current in DC
input 2 of module 1.
Check aux. code.
Check DC input connections
and sensor.
Check wiring and sensor.
57686
(0xe15
6)
Insulation resistance
device
Insulation resistance device has
not produced a valid measurement
in time.
Verify wiring and connection to
MIRU.
57687
(0xe15
7)
Grounding signal Grounding current signal is invalid. Check signal cable.
57688
(0xe15
8)
DC current
measurement faulty
DC current measurement is found
faulty. One or more DC current
measurement has/have failed.
Connection is lost or sensor is
broken. This check is done when
DC contactors are open.
Check DC connections and
sensor.
Check the active warnings in
the event log.
Check aux. code, to know
which module activated the
warning.
Check wiring and sensor.
57689
(0xe15
9)
SCADA
communication lost
SCADA communication lost.
Communication is lost if heartbeat
echo is not received within defined
time.
Verify that heartbeat is echoed
back to system. If echo interval
is too long, modify heartbeat
max interval with parameter
164.12 Heartbeat max interval.
57690
(0xe15
a)
SCADA
communication timeout
SCADA communication timeout.
Communication is lost when
heartbeat was not returned by
SCADA within define time of
specification.
Aux. code 4 indicates that
communication has returned but is
currently in timeout state.
Control commands are frozen
during timeout state.
Wait for communication timeout
to pass. Timeout length can be
configured with parameter
164.11 Comm hold-off after loss
event
57854
(0xe1fe
)
Autoreset Autoreset is active and is about to
reset inverter.
Autoreset resets faults after
defined time is elapsed.