54 Program features
Tabel 6: Customer external faults configuration
To configure a customer fault signal, select the correct source and settings. For example, if
a customer fault signal is connected to the digital input X20.x connector, configure the
following parameters:
Tabel 7: Example of customer external faults configuration
Settings
176.21 External fault 1 source...176.34 External fault 3 failure logic
Action type Set parameter...
Source for external fault 1 signal 176.21 External fault 1 source = Digital input X20.3 [4]
Active type in the event of external fault 1 176.22 External fault 1 action = Delayed fault [3]
Delay time to trigger the fault 1 action 176.23 External fault 1 action delay = 1 s
Fault 1 failure logic 176.24 External fault 1 failure logic = Active High