Parameters 79
130.65 P(f) release frequency Defines frequency above the nominal frequency when
limitation is released and ramping limit up is started.
0.20 Hz/ Real
0.00...30.00 Hz Release frequency 100 = 1 Hz
130.66 P(f) release time Defines delay time after frequency dropped below
release frequency before ramping limit up is started.
0 s/ Real
0...600 s Delay time 1 = 1 s
130.67 P(f) release ramp Defines active power ramping slope after releasing the
limit.
10%/min/
Real
5...600%/min Release ramp 1 = 1%/min
130.68 P(f) release ramp ref Selects release ramp reference of the P(f) limiter. Nominal/ List
Nominal Nominal power 1
Corner power Active power when the corner frequency has been
crossed.
2
Pdelta Power difference between the corner power and the
minimum limited power during P(f) limitation.
3
130.69 P(f) activation delay Sets delay time before activating the functionality. 0 ms/ Real
0...5000 ms Delay time 1 = 1 ms
130.70 Startup power ramp type Selects when to activate power ramping after grid
connection.
Off/ List
Off Power ramp is not activated. 0
After grid fault Power ramp only after grid fault occurred. 1
Always Power ramp always when connecting to grid. 2
130.71 Normal startup ramp Sets active power ramp used after normal grid
connection.
10%/min/
Real
0...600%/min Active power ramp. 1 = 1%/min
130.72 After grid fault startup
ramp
Sets active power ramp used in reconnection after grid
fault.
10%/min/
Real
0...600 %/min Active power ramp 1 = 1 %/min
130.73 FRT recovery Enables active power ramping after fault ride through. Disabled/ List
Disabled 0
Enabled 1
130.74 FRT recovery ramp Defines the active power ramp used after fault ride
through.
500 %/s/ List
10...1000 %/s Fault ride through recovery ramp 1 = 1 %/s
130.75 External power limit Defines external active power limit, e.g., from fieldbus. 200.0%/ Real
0.0...200.0 % External active power limit. 10 = 1 %
130.76 P(U) limiter Selects P(U) limiter type. Disabled/ List
Disabled P(U) limiter function is disabled. 0
Constant limit See Constant P(U) limitation (page 35). 1
Free running droop limit See Droop P(U) limitation curve (page 36). 2
Decremental droop limit See Droop P(U) limitation curve (page 36). 3
130.77 P(U) trigger level Defines P(U) trigger level. 110.0%/ Real
0.0...200.0 % P(U) trigger level. 10 = 1 %
130.78 P(U) release level Defines P(U) release level. 110%/ Real
0.0...200.0 % P(U) release level. 10 = 1 %
No. Name/Value Description Def/
FbEq16/32

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVS980-58 and is the answer not in the manual?

ABB PVS980-58 Specifications

General IconGeneral
BrandABB
ModelPVS980-58
CategoryInverter
LanguageEnglish

Related product manuals