IEC05000133-3-en.vsd
tMin
Current
Operate
time
IMin
IEC05000133 V2 EN-US
Figure 431: Minimum time-lag operation for the IEC curves
In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current start value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
The RI inverse time curve emulates the characteristic of the electromechanical
ASEA relay RI. The curve is described by equation
98:
[ ]
0.339 0.235
=
>
- ×
æ ö
ç ÷
ç ÷
ç ÷
è ø
k
t s
in
i
EQUATION1194 V1 EN-US
(Equation 98)
where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current
Section 23 1MRK 506 382-UEN A
Inverse time characteristics
894 Line distance protection REL650 2.2 IEC