EasyManua.ls Logo

Basler DECS-200 - Page 131

Basler DECS-200
181 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DECS-200 Setup 6-3
Enter the generator CT secondary current rating ......................................................................... ________
Enter the bus PT primary voltage rating (if applicable)................................................................. ________
Enter the bus PT secondary voltage rating (if applicable) ............................................................ ________
Enable or disable internal tracking................................................................................................ ________
Set the internal tracking delay (1 second is suggested) ............................................................... ________
Set the internal tracking traverse rate (10 seconds is suggested)................................................ ________
Enable or disable external tracking (applies only to redundant DECS-200 systems) .................. ________
Set the external tracking delay (applies only to redundant DECS-200 systems) ......................... ________
Set the external tracking traverse rate (applies only to redundant DECS-200 systems) ............. ________
Rated Data
Enter the generator and exciter field ratings and exciter-to-generator pole ratio settings illustrated in
Figure 6-3.
Figure 6-3. Rated Data Tab
Enter the rated generator terminal voltage ................................................................................... ________
Enter the rated generator current ................................................................................................. ________
Enter the rated generator power factor......................................................................................... ________
Enter the exciter-to-generator pole ratio ....................................................................................... ________
Enter the rated exciter field voltage ............................................................................................. ________
Enter the rated exciter field current............................................................................................... ________
Auxiliary Input
Configure the accessory input selections and settings illustrated in Figure 6-4.
Select either voltage or current as the accessory input type ........................................................ ________
Select either inner loop (AVR/FCR) or outer loop (var/PF) as the summing type ........................ ________
Enter the accessory input gain (multiplier) setting for AVR mode ................................................ ________
Enter the accessory input gain (multiplier) setting for FCR mode ................................................ ________

Table of Contents

Related product manuals