Modbus™ Communication DECS-200
7-22
47883-84
OEL loop gain (Kg), adjustable from 0 to 1000 in 0.1 increments RW R32_23
47885-86
UEL loop gain (Kg), adjustable from 0 to 1000 in 0.1 increments RW R32_23
47887-88
UEL integral gain (Ki), adjustable from 0 to 1000 in 0.1 increments RW R32_23
47889-90
Voltage matching loop gain (Kg), adjustable from 0 to 1,000 in 0.1
increments
RW R32_23
47891-92
AVR mode derivative time constant, adjustable from 0 to 1 in 0.01
increments
RW R32_23
47893 to
47905
Reserved for future C9 data Not
supported
Not
defined
47906-07
SCL loop gain (Kg), adjustable from 0 to 1,000 in 0.1 increments RW R32_23
47908-09
SCL loop gain (Ki), adjustable from 0 to 1,000 in 0.1 increments RW R32_23
47910-20
Reserved for future C9 data Not
supported
Not
defined
Holding Registers for Information Category C10
Table 7-20. Information Category C10 (Protective Functions Parameters)
Registers Data Description Access
Data
Format
47921-22
Field overvoltage level, adjustable from 1 to 325 Vdc in 1-volt
increments
RW R32_23
47923-24
Field overcurrent base level, adjustable from 0.1 to 16 Adc in 0.1-
amp increments
RW R32_23
47925-26
Stator undervoltage level, adjustable from 0 to 30,000 Vac in 1-volt
increments
RW R32_23
47927-28
Stator overvoltage level, adjustable from 0 to 30,000 Vac in 1-volt
increments
RW R32_23
47929-30
Field overvoltage time delay, adjustable from 0.2 to 30 seconds in
0.1-second increments
RW R32_23
47931-32
Field overcurrent time dial multiplier, adjustable from 0.1 to 20 in 0.1
increments
RW R32_23
47933-34
Stator undervoltage time delay, adjustable from 0.5 to 60 seconds in
0.1-second increments
RW R32_23
47935-36
Stator overvoltage time delay, adjustable from 0.1 to 60 seconds in
0.1-second increments
RW R32_23
47937
Field overvoltage alarm enable: 0 = disabled / 1 = enabled RW UI16
47938
Field overcurrent alarm enable: 0 = disabled / 1 = enabled RW UI16
47939
Stator undervoltage alarm enable: 0 = disabled / 1 = enabled RW UI16
47940
Stator overvoltage alarm enable: 0 = disabled / 1 = enabled RW UI16
47941-42
Reserved RW R32_23
47943-44
Reserved
RW R32_23
47945
Reserved
RW UI16