EasyManua.ls Logo

Basler DECS-200 - Off-Line and Excitation Performance Tests

Basler DECS-200
181 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DECS-200 Setup 6-13
Relay Setting
Configure the contact status and type settings illustrated in Figure 6-16.
Select the Relay #1 contact status as normally open (NO) or normally closed (NC) ................... ________
Configure the Relay #1 contact type as momentary, maintained, or latched ............................... ________
If the Relay #2 contact type is momentary, enter the open/closed contact duration .................... ________
Select the Relay #2 contact status as normally open (NO) or normally closed (NC) ................... ________
Configure the Relay #2 contact type as momentary, maintained, or latched ............................... ________
If the Relay #2 contact type is momentary, enter the open/closed contact duration .................... ________
Select the Relay #2 contact status as normally open (NO) or normally closed (NC) ................... ________
Configure the Relay #2 contact type as momentary, maintained, or latched ............................... ________
If the Relay #2 contact type is momentary, enter the open/closed contact duration .................... ________
Figure 6-16. Relay Setting Tab
OFF-LINE TESTS - TURBINE NOT SPINNING
In the following tests, control of the machine is demonstrated via BESTCOMS, front panel HMI, and user-
supplied, remote switches. These tests ensure that the machine is not stressed because of incorrect
wiring or faulty components. The parameters listed here are only temporary, initial settings.
Start/Stop Tests
Check the operation of the following start and stop controls.
BESTCOMS Metering Screen, Operation tab .............................................................................. ________
DECS-200 front panel................................................................................................................... ________
Remote switches........................................................................................................................... ________
With excitation off, check AVR/FCR transfer from the BESTCOMS, the front panel, and
remote switches ............................................................................................................................ ________

Table of Contents

Related product manuals