1-8 General Information DECS-200
Generator Overvoltage Protection
Pickup
Range: 0 to 30 kVac
Increment: 1.0 Vac
Time Delay
Range: 0.1 to 60 s
Increment: 0.1 s
Loss of Sensing Protection
Unbalance Generator Volts: 0 to 100%
Balanced Generator Volts: 0 to 100%
Time Delay
Range: 0 to 30 s
Increment: 0.1 s
Loss of Field Protection
Pickup
Range: 0 to 3,000,000 kvar
Increment: 1 kvar
Time Delay
Range: 0.0 to 9.9 s
Increment: 0.1 s
Soft Start Function
Setting Range
Soft Start Bias Level: 0 to 90% in 1% increments
Soft Start Bias Time Delay: 1 to 7,200 seconds in 1 second increments
Voltage Matching
Accuracy: Generator rms voltage is matched with the bus rms voltage to within
±0.5% of the generator voltage
On-Line Overexcitation Limiting
Response time: <3 cycles
High Current Level
Pickup Range: 0 to 30.0 Adc
Pickup Increment: 0.1 Adc
Time Range: 0 to 10 s
Time Increment: 1 s
Medium Current Level
Pickup Range: 0 to 20.0 Adc
Pickup Increment: 0.1 Adc
Time Range: 0 to 120 s
Time Increment: 1 s
Low Current Level
Pickup Range: 0 to 15 Adc
Pickup Increment: 0.1 Adc
Time Range: continuous