Modbus™ Communication DECS-200
7-14
Table 7-12. Information Category C2 (Metering)
Registers Data Description Access
Data
Format
b0 = loss of field, b1 = in SCL, b2 – b15 are unassigned
47308 to
47375
Reserved for C2 data
Holding Registers for Information Category C3
Table 7-13. Information Category C3 (Reporting)
Registers Data Description Access
Data
Format
47376 to
47500
Reserved for future C3 data Not
supported
Not
defined
Holding Registers for Information Category C4
Table 7-14. Information Category C4 (Control System Configuration Parameters)
Registers Data Description Access
Data
Format
47501-02
Generator rated frequency, selectable to be 50 or 60 Hz RW R32_23
47503-04
Generator PT primary voltage rating, adjustable from 1 to 30,000
Vac in 1 volt increments
RW R32_23
47505-06
Generator PT secondary voltage rating, adjustable from 1 to 240
Vac in 1 volt increments
RW R32_23
47507-08
Generator CT primary current rating, adjustable from 1 to 60,000
Aac in 1 amp increments
RW R32_23
47509-10
Generator CT secondary current rating, selectable to be 1 or 5 Aac RW R32_23
47511-12
Field current rating, adjustable from 1 to 18 Adc, in 0.1 amp
increments
RW R32_23
47513-14
Field voltage connections to isolation box, selectable to be 32V,
63V, 125V, 250V or 375V
RW R32_23
47515-16
Bus sensing PT primary rating, adjustable from 1 to 500,000 Vac in
1 volt increments
RW R32_23
47517-18
Bus sensing PT secondary rating, adjustable from 1 to 240 Vac in 1
volt increments
RW R32_23
47519-20
Reserved RW R32_23
47521-22
Reserved
RW R32_23
47523-24
Generator rated voltage, adjustable from 85 to 30,000 Vac in 1 volt
increments
RW R32_23
47525-26
Generator rated output current, adjustable from 10 to 60,000 Aac in
0.1 amp increments
RW R32_23
47527-28
Generator rated field voltage, adjustable from 1 to 400 Vdc in 1 volt
increments
RW R32_23
47529-30
Generator rated field current, adjustable from 0.1 to 9999.0 Adc in
0.1 amp increments
RW R32_23
47531-32
Nominal bus voltage, adjustable from 85 to 500,000 Vac in 1 volt RW R32_23