6-20 Setup DECS-200
Adjust PF for 0.9, lagging.............................................................................................................. ________
Perform a step response by changing PF setpoint to 0.85, lagging to determine stability........... ________
If necessary, increase the PF gain (KI and Kg terms) to decrease the response time.
Repeat the test.............................................................................................................................. ________
Conclusion Of Testing
Configure the excitation system with the required parameters. Once satisfactory performance is achieved,
save all information to EEPROM.