Modbus™ Communication DECS-200
7-20
Holding Registers for Information Category C8
Table 7-18. Information Category C8 (Limiter Parameters)
Registers Data Description Access
Data
Format
47801-02
On-line OEL high limit level, adjustable from 0.1 to 30 Adc in 0.1-
amp increments
RW R32_23
47803-04
Time allowed at on-line OEL high limit level, adjustable from 0 to 10
seconds in 1-second increments
RW R32_23
47805-06
On-line OEL medium limit level, adjustable from 0.1 to 20 Adc in
0.1-amp increments
RW R32_23
47807-08
Time allowed at on-line OEL medium limit level, adjustable from 0 to
120 seconds in 1-second increments
RW R32_23
47809-10
On-line low OEL low limit level, adjustable from 0.1 to 15 Adc in 0.1-
amp increments
RW R32_23
47811-12
Internal UEL curve’s starting point (reactive power level at 0 kW).
This should be 0 to allow the programmable UEL curve to be used.
RW R32_23
47813-14
Time allowed at off-line OEL high limit level, adjustable from 0 to 10
seconds in 1-second increments
RW R32_23
47815-16
Off-line OEL high limit level, adjustable from 0 to 30 Adc in 0.1-amp
increments
RW R32_23
47817-18
Off-line OEL low limit level, adjustable from 0 to 15 Adc in 0.1-amp
increments
RW R32_23
47819-20
1st UEL point real power value, adjustable from 0 to generator’s full
rating (in kW)
RW R32_23
47821-22
2nd UEL point real power value, adjustable from 0 to generator’s full
rating (in kW)
RW R32_23
47823-24
3rd UEL point real power value, adjustable from 0 to generator’s full
rating (in kW)
RW R32_23
47825-26
4th UEL point real power value, adjustable from 0 to generator’s full
rating (in kW)
RW R32_23
47827-28
5th UEL point real power value, adjustable from 0 to generator’s full
rating (in kW)
RW R32_23
47829-30
1st UEL point reactive power value, adjustable from 0 to generator’s
full rating (in kvar)
RW R32_23
47831-32
2nd UEL point reactive power value, adjustable from 0 to
generator’s full rating (in kvar)
RW R32_23
47833-34
3rd UEL point reactive power value, adjustable from 0 to generator’s
full rating (in kvar)
RW R32_23
47835-36
4th UEL point reactive power value, adjustable from 0 to generator’s
full rating (in kvar)
RW R32_23
47837-38
5th UEL point reactive power value, adjustable from 0 to generator’s
full rating (in kvar)
RW R32_23
47839-40
SCL high limit level, adjustable from 0 to 66,000 A in 0.1 A
increments
RW R32_23