DECS-200 Modbus™ Communication 7-21
Table 7-18. Information Category C8 (Limiter Parameters)
Registers Data Description Access
Data
Format
47841-42
Time allowed at SCL high limit level, adjustable from 0 to 60
seconds in 0.1 second increments.
RW R32_23
47843-44
SCL low limit level, adjustable from 0 to 66,000 A, in 0.1 A
increments
RW R32_23
47845-46
Takeover OEL offline high limit level, adjustable from 0 to 9,999 A in
0.1 A increments
RW R32_23
47847-48
Takeover OEL offline low limit level, adjustable from 0 to 9,999 A in
0.1 A increments.
RW R32_23
47849-50
Takeover OEL offline time dial, adjustable from 0.1 to 20, in 0.1
increments
RW R32_23
47851-52
Takeover OEL online high limit level, adjustable from 0 to 9,999 A in
0.1 A increments.
RW R32_23
47853-54
Takeover OEL online low limit level, adjustable from 0 to 9,999 A in
0.1 a increments.
RW R32_23
47855-56
Takeover OEL online time dial, adjustable from 0.1 to 20 in 0.1
increments
RW R32_23
47857 to
47860
Reserved for future C8 data Not
supported
Not
defined
Holding Registers for Information Category C9
Table 7-19. Information Category C9 (Control Loop Gain Parameters)
Registers Data Description Access
Data
Format
47861-62
Stability setting group number: 1 to 21, where groups 1 to 20 are
preprogrammed values and group 21 is user programmable
RW R32_23
47863-64
AVR/FCR mode proportional gain (Kp), adjustable from 0 to 1,000 in
0.1 increments
RW R32_23
47865-66
AVR/FCR mode integral gain (Ki), adjustable from 0 to 1,000 in 0.1
increments
RW R32_23
47867-68
AVR/FCR mode derivative gain (Kd), adjustable from 0 to 1,000 in
0.1 increments
RW R32_23
47869-70
OEL integral gain (Ki), adjustable from 0 to 1000 in 0.1 increments RW R32_23
47871-72
PF mode integral gain (Ki), adjustable from 0 to 1,000 in 0.1
increments
RW R32_23
47873-74
Var mode integral gain (Ki), adjustable from 0 to 1,000 in 0.01
increments
RW R32_23
47875-76
FCR mode loop gain (Kg), adjustable from 0 to 1,000 in 0.1
increments
RW R32_23
47877-78
AVR mode loop gain (Kg), adjustable from 0 to 1,000 in 0.1
increments
RW R32_23
47879-80
Var mode loop gain (Kg), adjustable from 0 to 1,000 in 0.01
increments
RW R32_23
47881-82
PF mode loop gain (Kg), adjustable from 0 to 1000 in 0.1 increments RW R32_23