EasyManua.ls Logo

Basler DECS-200 - Page 139

Basler DECS-200
181 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DECS-200 Setup 6-11
Figure 6-14. Protection Settings Tab
Enter the threshold for field overvoltage protection ...................................................................... ________
Enter the time delay for field overvoltage protection..................................................................... ________
Enter the percent of rated field current that indicates an open exciter diode ............................... ________
Enter the percent of rated field current that disables open- and shorted-diode protection .......... ________
Enter the annunciation time delay for open exciter diode protection............................................ ________
Enter the threshold for generator undervoltage protection ........................................................... ________
Enter the time delay for generator undervoltage protection ......................................................... ________
Enter the threshold for field overcurrent protection ...................................................................... ________
Enter the time delay for field overcurrent protection ..................................................................... ________
Enter the percent of rated field current that indicates a shorted exciter diode ............................. ________
Enter the annunciation time delay for shorted exciter diode protection........................................ ________
Enter the threshold for loss of field protection .............................................................................. ________
Enter the time delay for loss of field protection............................................................................. ________
Relay Logic
Review the excitation system interconnection drawings and verify the relay configurations. Relay logic
settings for each of the three DECS-200 programmable outputs are contained on two tabs with identical
configuration options. Only the tab for Relays 1 and 2 is illustrated here (Figure 6-15). Table 6-2 lists all of
the available functions that can be assigned to the programmable outputs. Checkmarks may be placed in
Table 6-2 to identify the functions assigned to each relay output.

Table of Contents

Related product manuals