DECS-200 Modbus™ Communication 7-25
Table 7-22. Information Category C12 (Relay Parameters)
Registers Data Description Access
Data
Format
48075
Reserved RW UI16
48076
16th annunciation enable for Relay 2 – Reserved for future C12 data RW UI16
48077
Output for Relay 2: 0 = contact open / 1 = contact closed R UI16
48078
Relay 2 annunciation type: 0 = momentary / 1 = maintained / 2 =
latched
RW UI16
48079
Relay 2 contact sense: 0 = closed for normal operation, open for
annunciation; 1 = open for normal operation, closed for annunciation
RW UI16
48080
Relay 2 output duration for momentary type, adjustable from 2 to 100
in unity increments (which is 0.1 to 5 seconds in 0.05 second
increments)
RW UI16
48081
b0 = field overvoltage, b1 = field overcurrent, b2 = gen. Undervoltage,
b3 = gen overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in
UEL, b7 = in FCR mode, b8 = loss of sensing voltage, b9 = setpoint
at lower limit, b10 = setpoint at upper limit, b11 = unassigned, b12 =
gen. Below 10 Hz, b13 = field overtemperature, b14-b15 are
unassigned.
RW UI16
48082
b0 = loss of field, b1 = in SCL, b2-b15 are unassigned RW UI16
48083
Reserved RW UI16
48084
Reserved RW UI16
48085
Reserved RW UI16
48086
Reserved RW UI16
48087
Reserved RW UI16
48088
Reserved RW UI16
48089
Reserved RW UI16
48090
Reserved RW UI16
48091
Reserved RW UI16
48092
Reserved RW UI16
48093
Reserved
RW UI16
48094
Reserved RW UI16
48095
Reserved RW UI16
48096
16th annunciation enable for Relay 3 - Reserved for future C12 data RW UI16
48097
Output for Relay 3: 0 = contact open / 1 = contact closed R UI16
48098
Relay 3 annunciation type: 0 = momentary / 1 = maintained / 2 =
latched
RW UI16
48099
Relay 3 contact sense: 0 = closed for normal operation, open for
annunciation; 1 = open for normal operation, closed for annunciation
RW UI16
48100
Relay 3 output duration for momentary type, adjustable from 2 to 100
in unity increments (which is 0.1 to 5 s in 0.05 s increments)
RW UI16