Learning Advanced Features
The table below list the available calculated conditions for the main
and auxiliary frequency references. Set the auxiliary reference gain with
bA.03 (Aux Ref Gain) to configure the auxiliary reference and set the
percentage to be reflected when calculating the main reference. Note
that items 4–7 below may result in either plus (+) or minus (-)
references (forward or reverse operation) even when unipolar analog
inputs are used.
Calculating final reference frequency
Main reference+(bA.03xbA.01xIn.01)
Main referencex(bA.03xbA.01)
Main reference/(bA.03xbA.01)
Main reference+{Main
referencex(bA.03xbA.01)}
Main reference+bA.03x2x(bA.01–50)xIn.01
Main referencex{bA.03x2x(bA.01–50)}
Main reference/{bA.03x2x(bA.01–50)}
Main reference+Main
referencexbA.03x2x(bA.01–50)
M: Main frequency reference (Hz or rpm)
G: Auxiliary reference gain (%)
A: Auxiliary frequency reference (Hz or rpm) or gain (%)
Adjust the gain of the auxiliary reference source selected in bA.01 (Aux
Ref Src).
Set one of the multi-function (digital) input terminals to 40 (dis Aux
Ref) and activate it to disable the auxiliary frequency reference. The
inverter will operate using the main frequency reference only.