Learning Protection Features
GM2 Series VFD
173
890054-00-00
Trip Status Reset
After a fault, the inverter can be reset using the Keypad (Stop/Reset) button or a digital
input.
Group
Code
Name
Setting
Setting Range
Unit
In
65~69
Px terminal setting
options
3
RST
-
-
Trip Status Reset Setting Details
Code and
Features
Description
In.65~69 Px
Define
Set the multi-function (digital) input terminal to 3 (RST) and activate the
terminal to reset the fault. A reset can also be performed by pressing
the [Stop/Reset] button on the keypad.
Operation Mode on Option Card Trip
The inverter monitors communication between installed option cards and will fault on an “Option
Trip” (OPt) when a communication error occurs. The inverter responds to an Option Trip based
on the setting of Pr.80 (motion at option trip).
Group
Code
Name
Setting
Setting Range
Unit
Pr
80
Motion selection at
option trip
0
None
02
-
1
Free-Run
2
Dec
Operation Mode on Option Trip Setting Details
Code and
Features
Description
Pr.80 Opt Trip
Mode
Configuration
Function
0
None
No operation.
1
Free-Run
The inverter output is blocked and fault
information is shown on the keypad.
2
Dec
The motor decelerates to the value set at Pr.07
(Trip Dec Time).