Learning Advanced Features
98
890054-00-00
GM2 Series VFD
Jog Operation
The jog operation allows for a temporary control of the inverter. There are two was to apply a jog
and start command using the multi-function (digital) input terminals.
Jog-1 using a digital input terminal set to JOG along with a start command (Fx or Rx).
Jog-2 using a single digital input set to FWD JOG or REV JOG.
Jog Operation 1-Forward
The jog operation is available in the forward (or reverse) direction, using two input terminals (Fx
and JOG). The table below lists parameter settings for a forward jog operation with a separate Run
(Fx) command.
Group
Code
Name
Setting
Setting Range
Unit
dr
11
Jog frequency
10.00
0.50Max Frequency
Hz
12
Jog run acceleration
time
20.00
0.00600.00
sec
13
Jog run deceleration
time
30.00
0.00600.00
sec
In
65
69
Px terminal setting
options
6
JOG
052
-
1
Fx
Forward Jog Description Details
Code and
Features
Description
In.65~69 Px Define
Select 6 (JOG) function from In.65 ~ 69 for one of the inputs.
[Terminal settings for jog operation]
dr.11 JOG Frequency
Set the operating frequency.
dr.12 JOG Acc Time
Set the acceleration speed.
dr.13 JOG Dec Time
Set the deceleration speed.
If a signal is applied to the jog terminal while running (FX applied), the operating frequency
changes to the jog frequency.