GM2 Series VFD
Perform Basic Operations
890054-00-00
Jog Frequency Configuration
The following demonstrates how to configure Jog Frequency by modifying code dr.11 (Jog
Frequency) in the Drive group from 10.00 Hz to 20.00 Hz. You can configure other parameters in
different groups exactly the same way.
Step
Instruction
Keypad Display
1
Go to parameter dr.11 in the Drive group.
2
Press the [ENT] key.
The current Jog Frequency value (10.00).
3
Press the [MODE/SHIFT] key 3 times to move to the tens'
position.
"1" in the tens' position will flash.
4
To make the target value "20.00", press the [] key to
change the tens' value to "2", and then press the [ENT]
key.
The selected value will flash on the display.
5
Press the [ENT] key again to save the changes.
Code dr.11 will be displayed. The parameter change has
been completed.
dr.11
10.00
10.00
20.00
dr.11
X 3