Set the Frequency Reference using V0, Built-in Potentiometer
You can modify the frequency reference using the built-in potentiometer. Set Frq
(Frequency reference source) to 4 (V0). View the frequency reference at the 0.00 (Main screen)
in the Operations group. Scaling of the V0 input is done with In.38 through In.41. View the
input voltage at In.35.
V0 Input Voltage Settings
Frequency reference source
Frequency for maximum analog
input
Time constant of V0 input filter
Output (%) at minimum voltage
Output (%) at maximum voltage
Changing rotation direction of V0
Setting the Reference Frequency using Input Current (I2)
You can modify the frequency reference using the I2 input terminal at the control board. Set Frq
(Frequency reference source) in the Operation group to 5 (I2) and apply 4–20 mA input current to
I2. Scaling of the input current range is done with In.53 through In.56. View the input current at
In.50.
Input Current (I2) Settings
Frequency reference source
Frequency for maximum analog
input
Time constant of I2 input filter
Output (%) at I2 minimum
current
Output (%) at I2 maximum
current
Changing rotation direction of I2
* Quantizing is disabled if "0" is selected.