Learning Protection Features
Fan Fault Detection Setting Details
Set the cooling fan fault mode.
The inverter output is blocked and the fan trip
(Fan) is displayed.
The inverter continues operation and the fan
warning (FanW) is displayed.
OU.31 Relay 1,
OU.33 Relay 2
Set either parameter OU.31 or OU.33 to 8 (FAN Warning), a fan
warning signal is output and operation continues. However,
the inverter will eventually trip on inverter overheat (OHt)
protection.
Lifetime diagnosis of Components
Lifetime Diagnosis for Fans
A fan exchange warning can be provided by entering a percentage at Pr.87 (Fan exchange warning
level). The % is based on 50,000 hours of operation. A fan exchange warning will appear on the
keypad or as a relay output when either Relay1 or Relay2 (OU.31 or OU.33) are set to 37 (FAN
Exchange).
The total fan usage level (%) appears at Pr.86. After exchanging fans, you can initialize the
accumulated % to 0 by setting Pr.88 (Fan reset time) to 1 (Yes). The Fan status bit can be viewed at
Pr.89.
Accumulated percent of
fan usage
Fan exchange warning
Level
Multi-function (digital)
relay1 item
Multi-function (digital)
relay2 item