Learning Protection Features
GM2 Series VFD
171
890054-00-00
Fan Fault Detection Setting Details
Code and
Features
Description
Pr.79 FAN
Trip Mode
Set the cooling fan fault mode.
Configuration
Function
0
Trip
The inverter output is blocked and the fan trip
(Fan) is displayed.
1
Warning
The inverter continues operation and the fan
warning (FanW) is displayed.
OU.31 Relay 1,
OU.33 Relay 2
Set either parameter OU.31 or OU.33 to 8 (FAN Warning), a fan
warning signal is output and operation continues. However,
the inverter will eventually trip on inverter overheat (OHt)
protection.
Lifetime diagnosis of Components
Lifetime Diagnosis for Fans
A fan exchange warning can be provided by entering a percentage at Pr.87 (Fan exchange warning
level). The % is based on 50,000 hours of operation. A fan exchange warning will appear on the
keypad or as a relay output when either Relay1 or Relay2 (OU.31 or OU.33) are set to 37 (FAN
Exchange).
The total fan usage level (%) appears at Pr.86. After exchanging fans, you can initialize the
accumulated % to 0 by setting Pr.88 (Fan reset time) to 1 (Yes). The Fan status bit can be viewed at
Pr.89.
Group
Cod
e
Name
Setting
Setting Range
Unit
Pr
86
Accumulated percent of
fan usage
0.0
0.06553.5
%
87
Fan exchange warning
Level
90.0
0.0100.0
%
88
Fan reset time
0
No
89
FAN Status
Bit
00 - 01
-
Bit
0
-
1
Fan Warning
OU
31
Multi-function (digital)
relay1 item
37
FAN Exchange
-
-
33
Multi-function (digital)
relay2 item