Frequency Setting (Keypad) and Operation (via Terminal Input)
Ensure that the first code of the Operation group is
selected, and code 0.00 (Reference frequency) is
displayed, then press the [ENT] key.
The first number on the right side of the display will flash.
Press the [MODE/SHIFT] key 3 times to move to the tens'
position.
"0" in the tens' place will flash.
Press the [▲] key to change it to 10.00, and then press
the [ENT] key.
The selected value will flash on the display.
Press the [ENT] key again to save the changes.
The reference frequency has been changed.
Refer to the wiring diagram at the bottom of the table,
and turn on the switch between the P1 (FX) and CM
terminals.
The RUN indicator light flashes and the FWD indicator
light comes on steady. The current acceleration frequency
is displayed.
When the frequency reference is reached (10 Hz), open
the switch between the P1 (FX) and CM terminals.
The RUN indicator light flashes again and the current
deceleration frequency is displayed.
When the frequency reaches 0 Hz, the RUN and FWD
indicator lights turn off, and the frequency reference,
10.00, is displayed again.
[Wiring Diagram] [Operation Pattern]
The instructions in the table are based on the factory default parameter settings. The
inverter may not work correctly if the default parameter settings were changed. In such
cases, initialize all parameters to reset the values to the factory default parameter settings
before following the instructions in the table (refer to 5.21 Parameter Initialization
on page 137).