Learning Protection Features
Inverter Overload Protection
In addition to motor overload settings, the inverters have built in inverter overload protection.
When the inverter input current exceeds the rated current, a protective function is activated to
prevent damages to the inverter. This inverter overload protection is based on inverse proportional
characteristics.
An inverter overload warning signal (relay output) can be provided before the inverter overload
protection function (IOL) operates. Set OU.31 or OU.33 to 6 (IOL). When the overcurrent time
reaches 60% of the allowed overcurrent time (150%, 1 min), the relay will change state (signal
output at 150%, 36 sec).
Multi-function (digital)
relay1 item
Multi-function (digital)
relay2 item
Speed Reference Loss
When setting the operating speed using an analog input, a pulsed input, through
communications option or the keypad, the speed reference loss setting can be used to
select the response of the inverter after the signal loss.
An output relay can be used to provide a signal when the speed reference is lost. Set OU.31 or
OU.33 to 13 (Lost Command).
Motion at reference frequency
loss
Time to determine reference
frequency loss
Operating frequency at
reference frequency loss
Start
frequency–
Max.
frequency
Analog input loss decision level
Multi-function (digital) relay1
item
Multi-function (digital) relay2
item