Fire Mode Operation
Fire Mode operation is for use in emergency situations. When enabled, Fire Mode allows the
inverter to provide continuous operation ignoring the majority of faults. Primarily used for fire
pump operation, but can be applied when continuous operation is required due to emergencies.
When enabled, Fire mode forces the inverter to ignore all minor faults and repeats a Reset/Restart
of major faults, regardless of the Reset/Restart count limit.
Fire Mode Parameter Settings
Fire Mode operation
count
Px terminal setting
options
Fire Mode Parameter Settings Details
When set to 1 (Fire Mode), enables Fire Mode operation
controlled with a digital input. When set to 2 (Fire Mode
Test), allows testing of Fire Mode operation.
Ad.81 Fire
Mode
frequency
Fire mode
frequency
reference
The frequency set at Ad. 81 (Fire mode frequency) is used
for the inverter operation in Fire mode. The Fire mode
frequency takes priority over the Jog frequency, Multi-step
frequencies, and the keypad input frequency.
Set the direction of motor rotation during Fire Mode
operation.
Counts the number of Fire Mode operations. Does not
increase count during Fire Mode testing.
ACC
Acc Time
Dec
Dec Time
During Fire Mode operation, the inverter accelerates and
decelerates based on the times set in ACC and Dec
parameters. When the Px terminal in activated, the inverter
accelerates based on the time set in ACC. When the Px
terminal is de-activated, the inverter decelerates based on
the time set in Dec.
Set to 51 (Fire Mode). When the digital input is activated,
the inverter will operate in Fire Mode.