Technical Specification
253
890054-00-00
GM2 Series VFD
Technical Specification
Input and Output Specification
240 V, 1 HP ~15 HP (0.75 kW 11 kW)
RSI-XXX-GM2.2C
001
002
003
005
007
010
015
240V,
3φ
Input
Normal
Duty,
120%
OL
HP
1
2
3
5
7.5
10
15
kW
0.75
1.5
2.2
4
5.5
7.5
11
Amps
3.1
6
9.6
12
18
30
40
KVA
1.2
2.3
3.8
4.6
6.9
11.4
15.2
Heavy
Duty,
150%
OL
HP
0.5
1
2
3
5
7.5
10
kW
0.4
0.75
1.5
2.2
4
5.5
7.5
Amps
2.5
5
8
11
17
24
32
KVA
1
1.9
3
4.2
6.5
9.1
12.2
240V,
1φ
Input
Normal
Duty
HP
-
0.75
1.5
2
3
5
7.5
Amps
2
3.6
5.9
6.7
9.8
16.3
22
Heavy
Duty
HP
-
0.5
1
1.5
3
3
5
Amps
1.5
2.8
4.6
6.1
9.3
12.8
17.4
Output frequency
0400 Hz. (IM Sensorless: 0120 Hz)
Output voltage (V)
3-phase 200240 V
Rated
input
Voltage (V)
3-phase 200240 VAC (-15% to +10%)
1-phase 240VAC (-5% to +10%)
Input frequency
3-phase 5060 Hz (5%)
1-phase 60Hz (5%)) only.
Rated
current
(A)
Normal
Duty
3
6.3
10.8
13.1
19.4
32.7
44.2
Heavy
Duty
2.2
4.9
8.4
11.8
18.5
25.8
34.9
Weight (lb /kg)
lbs
2.3
2.3
3
3
4.2
6.8
7.1
kg
1.04
1.06
1.36
1.4
1.89
3.08
3.21
Heat Dissipation (W)
22
45
79
117
208
281
382
Degree of Protection
IP20, UL Open (UL Type 1 achieved with optional conduit
box)
The standard motor capacity is based on a standard 4-pole motor.
The KVA rating is based on a 220V supply voltage for 240V inverters.
The rated output current is limited based on the carrier frequency set at Cn.04.
The output voltage is reducued 20%~40% during no-load operations to protect the
inverter from faults, 1 HP ~ 7.5 HP (0.4 ~ 4.0 kW) only.