Learning Advanced Features
Kinetic Energy Buffering - KEB
When the input power is disconnected, the inverter’s DC link voltage decreases, and a low voltage trip
occurs blocking the output. Kinetic energy buffering operation can be used to decelerate the motor
safely under these conditions. The inverter uses regenerative energy from the motor during the power
outage to maintain the DC link voltage. This extends the time for a low voltage trip to occur. For the KEB
feature to operate properly, parameter bA.19 (input voltage) must be set correctly.
Input power voltage
settings
Energy buffering selection
Energy buffering start level
Energy buffering stop level
Energy buffering Slip gain
Energy buffering
restoration frequency
Px terminal function setting
Kinetic Energy Buffering Operation Setting Details
Select the kinetic energy buffering operation when the input power is
disconnected. If KEB-1 or KEB-2 is selected, it controls the inverter's
output frequency and charges the DC link with regenerative energy
from the motor. KEB-1 operation will allow the inverter to resume
operation after power is restored. KEB-2 operation will decelerate the
motor to a safe stop.
KEB-1 can be activated with a digital input. Set Px terminal (In.65~69) to
52 (KEB-1 Select), and activate the terminal block upon power loss to
run the KEB-1 operation. If KEB-1 Select is selected via the terminal,
KEB-1 or KEB-2 cannot be set in Cn.77.
General deceleration is carried out until a low
voltage trip occurs.