Learning Advanced Features
94
890054-00-00
GM2 Series VFD
Operating with Auxiliary References
Frequency references can be configured with various calculated conditions that use the main and
auxiliary frequency references simultaneously. The main frequency reference (Frq) is used as the
operating frequency, while the auxiliary reference is used to modify and fine-tune the main
reference.
Group
Code
Name
Setting
Setting Range
Unit
Operation
Frq
Frequency reference
source
0
Keypad-1
08
-
bA
01
Auxiliary reference
source
1
V1
04
-
02
Auxiliary command
calculation type
0
M+(G*A)
07
-
03
Auxiliary frequency
reference gain
0.0
-200.0200.0
%
In
65 71
Px terminal setting
options
40
dis Aux Ref
052
-
Auxiliary Reference Setting Details
Code and
Features
Description
bA.01 Aux Ref
Src
Set the input type to be used for the auxiliary frequency reference.
Configuration
Function
0
None
Auxiliary frequency reference is disabled.
1
V1
Sets the V1 (voltage) terminal at the control
terminal block as the source of auxiliary frequency
reference.
3
V0
Select the potentiometer (volume dial) of keypad as
auxiliary command.
4
I2
Sets the I2 (current) terminal at the control terminal
block as the source of auxiliary frequency reference.