EasyManua.ls Logo

BENSHAW RSi GM2 Series - Multi-Function (Digital) Relay On;Off Control

BENSHAW RSi GM2 Series
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Learning Advanced Features
890054-00-00
GM2 Series VFD
141
Multi-function (digital) relay On/Off Control
This feature operates an output relay (Relay1 or Relay2) based on the analog input level.
Set the On level (Ad.67) to activate the relay and the Off level (Ad.68) to de-activate the
relay.
Group
Code
Name
Setting
Setting Range
Unit
Ad
66
Output terminal on/off
control mode
1
V1
-
-
67
Output contact On level
90.00
Output contact off level
100.00%
%
68
Output contact Off level
10.00
0.00Output terminal on
level
%
OU
31
Multi-function (digital)
relay1 item
34
On/Off
-
-
33
Multi-function (digital)
relay2 item
Multi-function (digital) relay On/Off Control Setting Details
Code and Features
Description
Ad.66 On/Off Ctrl Src
Select the analog input to use for On/Off control.
Ad.67 On-C Level,
Ad.68 Off-C Level
Set the On and Off levels for the output relay.