Actual Application Examples
Acceleration Time Configuration
The following demonstrates how to modify the Acceleration time (ACC) parameter value (from 5.0
to 16.0) in the Operation group.
Ensure that the first code of the Operation group is selected, and
code 0.00 (Reference frequency) is displayed.
Press the [▲] key.
The display will change to the ACC code in the Operation group.
Press the [ENT] key.
The number "5.0" will be displayed, with "0" flashing. This indicates
that the current acceleration time is set to 5.0 seconds. The flashing
value is ready to be modified by using the keypad.
Press the [MODE/SHIFT] key to shift to the required units position
(ones, tens, hundreds, etc.).
"5" in the ones' place from "5.0" will flash. This indicates the
flashing value, "5" is ready to be modified.
To make the target value "16.0", press the [▲] key to change the
ones' place value to "6".
Press the [MODE/SHIFT] key to move to the tens' position.
"0" in the tens' place from "06.0" will flash.
To make the target value "16.0", press the [▲] key to change the
tens' value to "1", and then press the [ENT] key.
The selected value will flash on the display.
Press the [ENT] key again to save the changes.
"ACC" will be displayed. The change to the acceleration time setup
has been completed.