EasyManua.ls Logo

BENSHAW RSi GM2 Series - Auto-Tuning

BENSHAW RSi GM2 Series
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Learning Advanced Features
890054-00-00
GM2 Series VFD
115
Auto-tuning
The motor parameters can be measured automatically and can be used for auto torque boost or
sensorless vector control.
Example - Auto-Tuning Based on 0.75kW, 200V, 60Hz, 4 Pole Motor
Group
Code
Name
Setting
Setting Range
Unit
dr
14
Motor capacity
1
0.75 kW
015
-
bA
11
Number of
motor poles
4
248
-
12
Rated slip speed
70
03000
Rpm
13
Motor rated
current
3.3
1.01000.0
A
14
Motor noload
current
1.7
0.51000.0
A
15
Motor rated
voltage
220
170480
V
16
Motor efficiency
83
64100
%
20
Auto tuning
0
None
-
-
21
Stator resistance
2.951
Depends on the motor
setting
Ω
22
Leakage
inductance
25.20
Depends on the motor
setting
mH
23
Stator
inductance
171.1
Depends on the motor
setting
mH
24
Rotor time
constant
137
255000
ms

Table of Contents