Command Source (Start/Stop) Configuration
The GM2 inverter provides several methods to Start and Stop the inverter. Choices include the
keypad, digital input terminals, RS-485 (Modbus), or Fieldbus option cards.
Setting the Keypad as a Command Input Device
The keypad can be selected as a command input device to start and stop the inverter. Set
parameter drv (command source) to 0 (Keypad). Press the [RUN] key on the keypad to start and the
[STOP/RESET] key to stop.
Setting the Terminal Block as a Command Input Device -
Fwd/Rev Run Commands
Digital input terminals can be selected as the command input device. Set parameter drv (command
source) to 1 (Fx/Rx-1). Choose (2) of the digital input terminals (P1 ~ P5) to setup as Forward and
Reverse. Set (2) of the correspondinig parameters (In.65~In.69) to 1 (Fx) and 2 (Rx) respectively.
Activating either terminal constitutes a run command. Activating both terminals constitutes a stop
command.
Px terminal
setting options
Fwd/Rev Command using Digital Input Terminals – Setting Details
Operation group
drv– Cmd Source
Assign a terminal for forward (Fx) operation.
Assign a terminal for reverse (Rx) operation.