Choose (3) of the digital input terminals (P1 ~ P5) to setup as multi-
step inputs. Set (3) of the correspondinig parameters (In.65~In.69) to 7
(Speed-L), 8 (Speed-M), or 9 (Speed-H).
Example using terminals P3, P4 and P5 set to Speed-L, Speed-M and
Speed-H respectively, the following multi-step operation will be
available.
[Multi-step operation]
Set the time for the inverter to check for other digital inputs. Set In.89
to 100 ms and when an input signal is received at P5, the inverter will
search for inputs at other terminals for 100 ms, before proceeding to
accelerate or decelerate based on P5’s configuration.