RS-485 Communication Features
183
890054-00-00
GM2 Series VFD
Code and Features
Description
CM.05 Resp Delay
Set the response time for the slave (inverter) to react to the request from the
master. Response time is used in a system where the slave device response is too
fast for the master device to process. Set this code to an appropriate value for
smooth master-slave communication.
Setting Start command and Frequency
Set the drv code of the operation group to 3 (Int 485) and the Frq code of the operation group to 6
(Int 485) in order to set the start command and frequency of the common area parameters via
communication.
Group
Code
Name
Setting
Setting Range
Unit
Operation
drv
Command Source
3
Int 485
04
-
Frq
Frequency reference
source
6
Int 485
08
-

Table of Contents