211
Table of Functions
890054-00-00
GM2 Series VFD
Advanced Function Group (PAR→Ad)
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
Ad.00
-
Jump Code
199
24
O
O
O
p.34
Ad.01
0h1301
Acceleration
pattern
0
Linear
0: Linear
X
O
O
p.72
1
S-curve
Ad.02
0h1302
Deceleration
pattern
0
Linear
0: Linear
X
O
O
p.72
1
S-curve
Ad.03
1
0h1303
S-curve
acceleration
start point
gradient
1100 (%)
40
X
O
O
p.72
Ad.04
1
0h1304
S-curve
acceleration
end point
gradient
1100 (%)
40
X
O
O
p.72
Ad.05
2
0h1305
S-curve
deceleration
start point
gradient
1100 (%)
40
X
O
O
p.72
Ad.06
2
0h1306
S-curve
deceleration
end point
gradient
1100 (%)
40
X
O
O
p.72
Ad.07
0h1307
Start Mode
0
Acc
0: Acc
X
O
O
p.80
1
Dc-Start
Ad.08
0h1308
Stop Mode
0
Dec
0:Dec
X
O
O
p.82
1
Dc-Brake
2
Free-Run
4
Power
Braking
Ad.09
0h1309
Run
prevention
options
0
None
0: None
X
O
O
p.64
1
Forward
Prev
2
Reverse
Prev
Ad.10
0h130A
Starting with
power on
0
No
0: No
O
O
O
p.65
1
Yes
Ad.12
3
0h130C
Start DC
braking time
0.0060.00 (s)
0
X
O
X
p.80
Ad.13
0h130D
Amount of
applied DC
0-Rated Current of
Inverter/Rated
Current of Motor x
100 (%)
50
X
O
X
p.83
Ad.14
4
0h130E
Output
blocking time
before DC
braking
0.0060.00 (s)
0.1
X
O
O
p.83
Ad.15
4
0h130F
DC braking
time
0.0060.00 (s)
1
X
O
O
p.83

Table of Contents