223
Table of Functions
890054-00-00
GM2 Series VFD
Output Terminal Block Function Group (PAR→OU)
Code
Comm.
Address
Name
Setting Range
Initial Value
Property*
V/F
SL
Ref.
OU.00
-
Jump Code
199
30
O
O
O
p.34
OU.01
0h1601
Analog
output 1
item
0
Frequency
0:
Frequency
O
O
O
p.143
1
Output Current
2
Output Voltage
3
DCLink Voltage
4
Torque
5
Output Power
6
Idse
7
Iqse
8
Target Freq
9
Ramp Freq
10
Speed Fdb
12
PID Ref Value
13
PID Fdb Value
14
PID Output
15
Constant
OU.02
0h1602
Analog
output 1
gain
-1000.01000.0 (%)
100
O
O
O
p.143
OU.03
0h1603
Analog
output 1
bias
-100100 (%)
0
O
O
O
p.143
OU.04
0h1604
Analog
output 1
filter
010000 (ms)
5
O
O
O
p.143
OU.05
0h1606
Analog
constant
output1
0.0100.0 (%)
0
O
O
O
p.143
OU.06
0h1606
Analog
output1
monitor
0.01000.0 (%)
0
-
O
O
p.143
OU.30
0h161E
Fault output
item
bit
000111
10
[1]
O
O
O
p.151
1
Low voltage
2
Any faults other
than low voltage
3
Final failure of
automatic restart
OU.31
0h161F
Multi-
function
(digital)
relay1 item
0
None
29: Trip
O
O
O
p.151
1
FDT-1
2
FDT-2
3
FDT-3
4
FDT-4
5
Over Load
6
IOL
7
Under Load
8
Fan Warning
9
Stall

Table of Contents