Setting the Frequency Reference using RS-485 Communication
Set parameter Frq (Frequency reference source) 6 (Int 485). Control the inverter with upper-level
controllers (PCs or PLCs) via RS-485 communications using the (S+/S-) input terminals of the
control board. Refer to 7 RS-485 Communication Features on page 179 for more details.
RS-485 Communication Settings
Frequency reference source
Built-in communication
inverter ID
Built-in communication
protocol
Built-in communication speed
Built-in communication frame
setting
Frequency Hold by Digital Input
When using an analog input as the frequency reference, you can apply a hold of the output
frequency at any point. Set a digital input to 21 (Analog Hold). When the input is activated, the
output frequency will be maintained (held constant) until the input is de-activated.