Setting Acceleration and Deceleration Times
Acc/Dec Time Based on Maximum Frequency
Acc/Dec times are based on maximum frequency (bA.08 set to 0 (MaxFreq)), not on inverter
operating frequency. Acceleration time set at ACC refers to the time required for the inverter to
reach the maximum frequency from a stopped (0 Hz) state. Likewise, deceleration time set at dEC
refers to the time required to decelerate from the maximum frequency to a stopped state (0 Hz).
Acc/Dec reference
frequency
Acc/Dec Time Based on Maximum Frequency – Setting Details
bA.08
Acc/Dec
reference
frequency
Set bA.08 to 0 (Max Freq) to setup Acc/Dec time based on maximum
frequency.
Set the Acc/Dec time based on maximum
frequency.
Set the Acc/Dec time based on operating
frequency.
Example: maximum frequency is 60.00 Hz, the Acc/Dec times are set to
5 seconds. With a frequency reference of 30 Hz, the time required to
reach 30 Hz is 2.5 seconds.
Set the time scale for all time-related values. Set to 0 (0.01sec) when
more precise Acc/Dec times are required. Set to 2 (1sec) when the time
display and setting require less precision or need to be extended
above 60.00 secs.
Sets 0.01 second as the minimum unit.
Sets 0.1 second as the minimum unit.
Sets 1 second as the minimum unit.