EasyManua.ls Logo

BENSHAW RSi GM2 Series - Heat Emission

BENSHAW RSi GM2 Series
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specification
890054-00-00
266
GM2 Series VFD
Heat Emission
The following table provides data on the heat generated by the inverters. Heat emissions are based
on operation at room temperature and the carrier frequency set at default.
Inverter Capacity
Efficiency
(%)
Total
Losses
(W)
Internal
Losses
(W)
External
Losses
(W)
Normal Duty
Heavy Duty
kW
HP
Amps
kW
HP
Amps
3-phase
240V
0.75
1
3.1
0.4
0.5
2.5
96.40
22
17
6
1.5
2
6
0.75
1
5
96.40
45
17
28
2.2
3
9.6
1.5
2
8
96.70
79
17
62
4
5
12
2.2
3
11
96.70
117
17
99
5.5
7.5
18
4
5
17
96.80
208
18
190
7.5
10
30
5.5
7.5
24
96.90
281
19
262
11
15
40
7.5
10
32
96.90
382
19
364
3-phase
480V
0.75
1
2
0.4
0.5
1.3
96.00
24
17
7
1.5
2
3.1
0.75
1
2.5
96.80
42
17
24
2.2
3
5.1
1.5
2
4
97.30
71
18
53
4
5
6.9
2.2
3
5.5
97.50
99
18
81
5.5
7.5
10
4
5
9
97.60
176
19
157
7.5
10
16
5.5
7.5
12
97.80
231
20
211
11
15
23
7.5
10
16
97.80
315
20
295

Table of Contents