Preparing the Installation
890054-00-00
4
GM2 Series VFD
Installation Considerations
Inverters are composed of various precision electronic devices and the installation environment can
significantly impact the lifespan and reliability of the product. The table below details the ideal
installation and operating conditions for the inverter.
Items
Description
Ambient
temperature*
Normal Duty: 14°F ~ 104°F (-10~40)
Heavy Duty: 14°F ~ 122°F (-10~50)
Ambient
humidity
Less than 95% relative humidity (no condensation)
Storage
temperature
-4°F ~ 149°F (-20~65°C)
Environmental
factors
An environment free from corrosive or flammable gases, oil residue, and
dust
Operating
altitude
Vibration
Lower than 3,280 ft (1,000 m) above sea level
(Apply derating of 1% on voltage/output current for every 328 ft. (100m)
above 3,280 ft. (1,000 m), maximum of 13123 ft. (4,000m).
Less than 1G (9.8 m/sec
2
)
Air Pressure
70106 kPa
* The ambient temperature is the temperature measured at a point 2” (5 cm) from the surface of
the inverter.
Do not allow the ambient temperature to exceed the allowable range while operating the
inverter.