RS-485 Communication Features
185
890054-00-00
GM2 Series VFD
Saving Parameters Defined by Communication
If you turn off the inverter after setting the common area parameters or keypad parameters via
communication, the changes are lost and the values revert to the previous setting.
Set address 0h03E0 to 0 and then set it again to 1 via communication saves the existing parameter
settings. However, setting address 0h03E0 to 1 and then setting it to 0 does not carry out the
same function.
Total Memory Map for Communication
Communication Area
Memory Map
Description
Communication common
compatible area
0h00000h00FF
GM2 compatible area
Parameter registration type area
0h01000h01FF
Areas registered at CM.3138 and CM.51
58
GM2 communication
common area
0h03000h037F
Inverter monitoring area
0h03800h03DF
Inverter control area
0h03E00h03FF
Inverter memory control area
0h04000h0FFF
Reserved
0h1100
dr Group
0h1200
bA Group
0h1300
Ad Group
0h1400
Cn Group
0h1500
In Group
0h1600
OU Group
0h1700
CM Group
0h1800
AP Group
0h1B00
Pr Group
0h1C00
M2 Group
Parameter Group for Data Transmission
By defining a parameter group for data transmission, the communication addresses registered in
the communication function group (CM) can be used in communication. Parameter group for data
transmission may be defined to transmit multiple parameters at once, into the communication
frame.
Group
Code
Name
Setting
Setting Range
Unit
CM
3138
Output communication
address x
-
0000FFFF
Hex
5158
Input communication
address x
-
0000FFFF
Hex
Currently Registered CM Group Parameter
Comm. Address
Parameter
Assigned Content by Bit
0h01000h0107
Status Parameter-1
Status Parameter-8
Parameter communication code value registered at
CM.3138 (Read-only)
0h01100h0117
Control Parameter-1
Control Parameter-8
Parameter communication code value registered at
CM.5158 (Read/Write access)