Learning Advanced Features
Parameter Save
Changes to parameter settings in the compatible common area are not saved in the inverter
memory. If power is cycled, changes will be lost. Set dr.92 to 1 (Parameter Save) to save the
changed parameters into the inverter memory. The parameters cannot be saved if the inverter is
operating.
Parameter Initialization
The parameters changed by the user can be initialized to the factory default settings. Initialize
parameters in all groups by selecting 1 (All GRP) or select specific groups . The parameters cannot
be initialized if the inverter is operating or during a fault condition.
Parameter Initialization Setting Details
Initialize all data. Select 1 (All Grp) and
press [PROG/ENT] key to start
initialization. On completion, 0 (No) will
be displayed.
Initialize data by groups. Select initialize
group and press [PROG/ENT] key to start
initialization. On completion, 0 (No) will
be displayed.
Initialize Operation
Group