Safe Operation mode
This safety feature is used as a Run Enable/Disable input. When a digital input is set to 13 (Run
Enable), the inverter will only operate when the input is closed (Enabled). The input must be closed
to recognize other digital input functions. This feature is also useful for interlocking operation with
other equipment.
A stop mode can be selected (Ad.71, Run Dis Stop) if the Run Enable input is opened during
operation. Selections include coasting to a stop, Quick Stop and Quick Stop Resume. The
deceleration time (Ad.72, Q-Stop Time) can be set for the Quick Stop functions..
Group
Code
Name
Setting
Setting Range
Unit
In
65~69
Px terminal
setting options
13
RUN Enable
0-52
Ad
70
Safe operation
selection
0
Always Enable
0-1
1
DI Dependent
71
Safe operation
stop options
0
Free-Run
02
-
72
Safe operation
deceleration time
5.0
0.0600.0
sec
Safe Operation Mode Setting Details
Code and
Features
Description
In.65~69 Px
Define
Set one of the multi-function (digital) input terminals to 13 (RUN
Enable) to operate in safe operation mode.
Ad.70 Run En
Mode
Configuration
Function
0
Always Enable
Enables safe operation mode. Input must be
closed (Enabled) to operate.
1
DI Dependent
Operation is in combination with the status
of Run command (Fx input).
Ad.71 Run Dis
Stop
Set the stop method of the inverter when the Enable input terminal in
opened during operation.
Configuration
Function
1
Free-Run
Blocks the inverter output. Motor coasts to a
stop.
2
Q-Stop
Decelerates the motor based on the
deceleration time (Q-Stop Time) set in Ad.72.
When stopped, the Run command must be
reapplied to restart the inverter even if the
Enable input is closed (Enabled).
3
Q-Stop
Resume
Decelerates the motor based on the
deceleration time (Q-Stop Time) set in Ad.72. If
the Enable input is re-applied during
deceleration and the run command is
maintained, the inverter will resume normal
operation.
Ad.72 Q-Stop
Time
Sets the deceleration time when Ad.71 (Run Dis Stop) is set to 1 (Q-
Stop) or 2 (Q-Stop Resume).