Learning Advanced Features
Safe Operation mode
This safety feature is used as a Run Enable/Disable input. When a digital input is set to 13 (Run
Enable), the inverter will only operate when the input is closed (Enabled). The input must be closed
to recognize other digital input functions. This feature is also useful for interlocking operation with
other equipment.
A stop mode can be selected (Ad.71, Run Dis Stop) if the Run Enable input is opened during
operation. Selections include coasting to a stop, Quick Stop and Quick Stop Resume. The
deceleration time (Ad.72, Q-Stop Time) can be set for the Quick Stop functions..
Px terminal
setting options
Safe operation
stop options
Safe operation
deceleration time
Safe Operation Mode Setting Details
Set one of the multi-function (digital) input terminals to 13 (RUN
Enable) to operate in safe operation mode.
Enables safe operation mode. Input must be
closed (Enabled) to operate.
Operation is in combination with the status
of Run command (Fx input).
Set the stop method of the inverter when the Enable input terminal in
opened during operation.
Blocks the inverter output. Motor coasts to a
stop.
Decelerates the motor based on the
deceleration time (Q-Stop Time) set in Ad.72.
When stopped, the Run command must be
reapplied to restart the inverter even if the
Enable input is closed (Enabled).
Decelerates the motor based on the
deceleration time (Q-Stop Time) set in Ad.72. If
the Enable input is re-applied during
deceleration and the run command is
maintained, the inverter will resume normal
operation.
Sets the deceleration time when Ad.71 (Run Dis Stop) is set to 1 (Q-
Stop) or 2 (Q-Stop Resume).