Q-Stop Function
When Ad.70 (Run En Mode) is set to 1 (DI Dependent) and Ad.71 is set to 2 (Q-Stop), if the Run
Enable input is opened during operation, the inverter will decelerate to a stop based on the time
set in Ad.72, Q-Stop Time. To re-start, the Enable input must be re-applied and the Run command
(Fx) must be removed then re-applied.
Q-Stop Resume Function
The Quick Start resume function operates as follows:
When Ad.70 (Run En Mode) is set to 1 (DI Dependent) and Ad.71 is set to 3 (Q-Stop
Resume), this allows operation (Start/Stop) of the inverter based on the Run Enable
input. If the Run Enable is opened during operation and the Run command (Fx) is
maintained, closure of the Run Enable input will allow the inverter to operate (resume
operation).