Learning Basic Features
Multi-step Frequency Configuration
Multi-step operations (Fixed Speed Inputs) can be assigned to the Px terminals. Step 0 uses the
frequency reference source set with Frq in the Operations group. Steps 1 through 7 can be
configured using (3) digital input terminals. Set Px terminals to 7 (Speed-L), 8 (Speed-M) and 9
(Speed-H). These are recognized as binary inputs (000 ~ 111) and work in combination with Fx or
Rx run commands. The inverter operates according to the frequencies set with parameters St1, St2
and St3 (step frequencies 1~3) and bA.53 ~ bA.56 (step frequencies 47). and the binary command
combinations.
Multi-step Frequency Settings
Group
Code
Name
Setting
Setting Range
Unit
Operation
St1~St3
Multi-step
frequency 13
-
0Max Frequency
Hz
bA
5356
Multi-step
frequency 47
-
0Max Frequency
Hz
In
6569
Px terminal
setting options
7
Speed-L
052
-
8
Speed-M
-
9
Speed-H
-
89
Multi-step
command delay
time
1
15000
ms
Multi-step Frequency Setting Details
Code and
Features
Description
Operation group
St1~St3
Configure multi-step frequencies 13.
bA.53 ~ bA56
Step Freq 47
Configure multi-step frequencies 47.