Multi-step Frequency Configuration
Multi-step operations (Fixed Speed Inputs) can be assigned to the Px terminals. Step 0 uses the
frequency reference source set with Frq in the Operations group. Steps 1 through 7 can be
configured using (3) digital input terminals. Set Px terminals to 7 (Speed-L), 8 (Speed-M) and 9
(Speed-H). These are recognized as binary inputs (000 ~ 111) and work in combination with Fx or
Rx run commands. The inverter operates according to the frequencies set with parameters St1, St2
and St3 (step frequencies 1~3) and bA.53 ~ bA.56 (step frequencies 4–7). and the binary command
combinations.
Multi-step Frequency Settings