Learning Protection Features
Torque Detection Protection Action
The inverter monitors and detects over and under torque conditions. This feature is activated when
either Relay1 and/or Relay2 (OU.31 and/or OU.33) are set to 43 (Torque Detect 1) and/or 44
(Torque Detect 2). The torque levels and time delays are set in parameters OU.68, 69 or OU.71, 72.
The inverter responds to the over/under torque condition based on the setting of OU.67 and
OU.70. Selections include providing a warning or a trip, at a specific speed or throughout the speed
range.
Multi-function (digital)
relay1 item
Multi-function (digital)
relay2 item
Torque detection 1
operation setting
Torque detection 1 delay
time
Torque detection 2
operation setting
Torque detection 2 delay
time
*Visible only when the multi-function (digital) relay (OU.31, 33) is set to 43 (Prt Trq Det 1).
**Visible only when the multi-function (digital) relay (OU.31, 33) is set to 44 (Prt Trq Det 2).
The over and under torque detection action operates as shown in the figure by having a hysteresis
level of 10% compared to the motor's rated current. The over and under torque detection level set
as OU.68, OU.71 parameters are set as the ratio on motor's rated current.
Over Torque Detection Action
OUT-68 or OUT-71
OUT-69 or OUT-72
Motor
Current
MO
(42: Prt Trq Dect1
or 43: Prt Trq Dect2)
hysteresis(10%)
OUT-69 or OUT-72
hysteresis(10%)
Multi-function
output setting
Torque detection delay
time
Torque detection delay
time
43: Trq Dect1
44: Trq Dect2