RS-485 Communication Features
Command Loss Protective Operation
Configure the command loss decision standards and protective operations run when a
communication problem lasts for a specified period of time.
Command Loss Protective Operation Setting Details
Pr.12 Lost Cmd
Mode,
Pr.13 Lost Cmd
Time
Select the operation to (1) Free-Run when a communication error has occurred
and has exceeded the time set at Pr.13.
The reference frequency immediately becomes
the operating frequency without any protection
function.
The inverter blocks output. The motor performs in
free-run condition.
The motor decelerates and then stops.
The inverter continues in the reference frequency
input before the loss of speed.
The inverter continues in the operating frequency
before the loss of speed.
The inverter operates at the frequency set at Pr.
14 (Lost Preset F).
Setting Virtual Multi-function (digital) Input
Multi-function (digital) inputs can be controlled using a communication address (0h0385). Set
codes CM.70 ~ 77 to the functions to operate, and then set the BIT relevant to the function to 1 at
0h0322 to operate it. Virtual multi-function (digital) inputs operate independently from In.65–69
digital multi-function (digital) inputs and cannot be set redundantly. Virtual multi-function (digital)
inputs can be monitored using CM.86 (Virt Dl Status). Before you configure the virtual multi-
function (digital) inputs, set the DRV code according to the command source.
Communication multi-function
(digital) input x
Communication multi-function
(digital) input monitoring
Example: When sending an Fx command by controlling virtual multi-function (digital) input in the
common area via Int485, set CM.70 to FX. Then, assign a 0h0001 value to the communication
address 0h0322 to operate the forward direction operation (Fx) feature.
NOTE: The following are values and functions that are applied to address 0h0322: