Multi-step Acc/Dec Time Configuration
Digital input terminals can be configured for different Acc and Dec times. Up to 7 acceleration
times and 7 deceleration times can be set. Choose (up to 3) digital input terminals (P1 ~ P5) and
set the corresponding parameters (In.65~In.69) to 11 (XCEL-L), 12 (XCEL-M) and 49 (XCEL-H). These
are recognized as binary inputs (000 ~ 111). Acc times and Dec times are set with bA.70 through
bA.83.