70
GM2 Series VFD
890054-00-00
Learning Basic Features
Code and
Features
Description
In.65 ~ In.69
Px Define
(P1P5)
Choose and configure the terminals to use for multi-step Acc/Dec time
inputs.
Configuration
Function
11
XCEL-L
Acc/Dec command-L
12
XCEL-M
Acc/Dec command-M
49
XCEL-H
Acc/Dec command-H
Acc/Dec commands are recognized as binary code inputs and will
control the acceleration and deceleration based on parameter values
set with bA.70 ~ bA82 and bA.71 ~ bA83.
Example: P4 and P5 terminals are set as XCEL-L and XCEL-M
respectively, the following operation will be available.
Acc/Dec time
P5
P4
0
-
-
1
-
2
-
3
[Configuration of multi-function (digital) terminals P4 and P5]
In.89
InCheck Time
Set the time for the inverter to check for other digital inputs. Set In.89
to 100 ms and when an input signal is received at P4 or P5, the inverter
will search for inputs at other terminals for 100 ms, before proceeding
to accelerate or decelerate based on P4 or P5’s configuration.

Table of Contents