In.65 ~ In.69
Px Define
(P1–P5)
Choose and configure the terminals to use for multi-step Acc/Dec time
inputs.
Acc/Dec commands are recognized as binary code inputs and will
control the acceleration and deceleration based on parameter values
set with bA.70 ~ bA–82 and bA.71 ~ bA–83.
Example: P4 and P5 terminals are set as XCEL-L and XCEL-M
respectively, the following operation will be available.
[Configuration of multi-function (digital) terminals P4 and P5]
Set the time for the inverter to check for other digital inputs. Set In.89
to 100 ms and when an input signal is received at P4 or P5, the inverter
will search for inputs at other terminals for 100 ms, before proceeding
to accelerate or decelerate based on P4 or P5’s configuration.