When brake control is activated, DC braking (Ad.12) at inverter start and dwell operation
(Ad.20~23) do not operate.
• Brake release sequence: When a run command is applied, the inverter accelerates up
to brake release frequency (Ad.44 Forward or Ad.45 Reverse). After reaching the brake
release frequency, when the motor current reaches brake release current (Ad.41 BR Rls
Curr), the output relay (OU.31 or OU.33) set to 35 (BR Cotrol) sends a release signal.
Once the signal has been sent, acceleration will begin after maintaining frequency for
brake release delay time (Ad.42 BR Rls Dly).
• Brake engage sequence: When a stop command is applied, the motor decelerates.
When the output frequency reaches brake engage frequency (Ad.47 BR Eng Fr), the
motor stops deceleration and the output relay (OU.31 or OU.33) set to 35 (BR Cotrol)
sends a brake engage signal. Frequency is maintained for the brake engage delay time
(Ad.46 BR Eng Dly) and will become 0 afterwards. If Stop Mode (Ad.08) is set to 1 (DC
brake), inverter output is blocked after DC braking.