GM2 Series VFD
890054-00-00
Learning Basic Features
Stopping the Acc/Dec Operation
Configures a digital input terminal to stop acceleration or deceleration and operate the inverter at
a fixed frequency.
Group
Code
Name
Setting
Setting Range
Unit
In
65~69
Px terminal
25
XCEL Stop
052
-
V/F Control
Configure the inverter’s output voltages, gradient levels and output patterns to achieve a target
output frequency with V/F control. The amount of torque boost used during low frequency
operations can also be adjusted.
Linear V/F Pattern Operation
A linear V/F pattern (also refered to as scaler V/Hz.) configures the inverter output voltage and
frequency to increase or decrease at a fixed rate throughout the speed range. This V/F
characteristic is refered to as a constant V/F ratio (or V/Hz.) and is applied to loads that require
constant torque regardless of the speed.
Group
Code
Name
Setting
Setting Range
Unit
dr
09
Control mode
0
V/F
04
-
18
Base frequency
60.00
30.00400.00
Hz
19
Start frequency
0.50
0.0110.00
Hz
bA
07
V/F pattern
0
Linear
03
-