Up-down Operation
The inverter can control the speed of the motor using digital inputs set to the Up and Down
functions. The Up/Down operation can be applied to systems that use upper-lower limit switches.
Three digital inputs are required. One set to U/D Enable, and the other two for Up (increase speed)
and Down (decrease speed) operation.
The Up/Down operation will operate only when a multi-function (digital) terminal set to 27
(U/D Enable) is activated. The operation will follow the Up or Down inputs and will override other
speed reference inputs. When the U/D Enable input is De-activated, the inverter will respond to the
selected speed reference source.
If the frequency reference source parameter (Frq) is set as keypad, the frequency cannot be
programmed using the keypad when U/D Enable terminal is activated.